Honeywell LyricTM T6Pro Wi-Fi Programmable Thermostat user manual

Thermostats

Professional Install Guide

Package Includes:

• Lyric T6 PRO Wi-Fi Thermostat

• UWPTM Mounting System

• Honeywell Standard Installation Adapter (J-box adapter)

• Honeywell Decorative Cover Plate – Small; size 4-49/64 in = 121mm.

• Screws and anchors

• Professional Install Guide

• Getting Started Guide

Compatibility

• Compatible with most heating, cooling, and heat pump systems
• Required: 24 VAC power (“C”wire)
• Does not work with electric baseboard heat (120-240V)
• Does not work with millivolt systems
• Android oriOS smartphone ortablet

UWP Mounting System installation

1.Open package to find the UWP.

  1. Position the UWP on the wall. Level and mark hole positions.

Drill holes at marked positions, and then lightly tap supplied wall anchors into wall using a hammer. Drill 7/32” holes for drywall.

  1. Pull the door open and insert wires through wiring hole of the UWP.
  1. Place the UWP over the wall anchors. Insert and tighten mounting screws supplied with the UWP. Do not overtighten. Tighten until the UWP no longer moves. Close the door.

Optional Decorative Cover Plate installation

Use the Optional Cover Plate when:

• Mounting the thermostat to an electrical junction box
• Or when you need to cover paint gap from the old thermostat.

  1. Separate the Junction Box Adapter from the Cover Plate.
  1. Mount the Junction Box Adapter to the wall or an electrical box using any of the eight screw holes. Insert and tighten mounting screws supplied with Cover Plate Kit. Do not overtighten. Make sure the Adapter Plate is level.
  1. Attach the UWP by hanging it on the top hook of the Junction Box Adapter and then snapping the bottom of the UWP in place.
  1. Snap the Cover Plate onto the Junction Box Adapter.

Wiring UWP

Push down on the tabs to put the wires into the inner holes of their corresponding terminals on the UWP (one wire per terminal) until they are firmly in place. Gently tug on the wires to verify they are secure. If you need to release the wires again, push down the terminal tabs
on the sides of the UWP.

Terminal designations

Conventional Systems Heat pump systems
Terminal Description Terminal Description
S/S Input for a wired indoor,  outdoor sensor S/S Input for a wired indoor,  outdoor sensor
Compressor Stage 1 Compressor Stage 1
Y2 Compressor Stage 2 Y2 Compressor Stage 2
Fan Relay Fan Relay
C24VAC Common wire from  secondary side of cooling  transformer (if 2 transformers)C24VAC Common wire from  secondary side of cooling  transformer
K* Connect to K on Wire Saver  Module K* Connect to K on Wire Saver  Module
U/U** Relay for ventilation U/U** Relay for ventilation
L/A Connect to compressor  monitor
Heat Stage 1 O/B Changeover valve for heat  pumps
W2 Heat Stage 2 Aux Backup Heat
Emergency Heat
24 VAC Heating transformer 24 VAC Heating transformer
Rc 24 VAC Cooling transformer Rc 24 VAC Cooling transformer
  • The THP9045A1023 Wire Saver Module is used on heat/cool systems when you only have four wires at the thermostat and you need a fifth wire for a common wire. Use the K terminal in place of the Y and G terminals on conventional or heat pump systems to provide control of the fan and the compressor through a single wire—the unused wire then becomes your common wire. See THP9045 instructions
    for more information.

** Ventilation is not available on all models. When the U slider is in the down position (2 wires), the U contacts are a dry set of contacts. If your ventilation system requires 24 volts, move the U slider to the up position (1 wire). Lower U terminal is internally jumped to the Rc terminal. In this application, you would hook up one wire from your damper to the upper U terminal and the other to the common side of
the transformer.

Setting Slider Tabs

Set R Slider Tab, see Figure 9.

• Use built-in jumper (R Slider Tab) to differentiate between one or two transformer systems.
• If there is only one R wire, and it is connected to the R, Rc, or RH terminal on the old thermostat, set the slider to the up position (1 wire).
• If there is one wire connected to the R terminal and one wire connected to the Rc terminal, set the slider to the down position (2 wires).

Set U Slider Tab, see Figure 10.

• Use built-in jumper (U Slider Tab) of relay to wire ventilation. Please note that ventilation is not supported on all models.
• When the U Slider Tab is in the down position (2 wires) the U contacts are a dry set of contacts.
• If the ventilator is powered by the cooling transformer, move the jumper switch to the up position (1 wire). With this switch set to 1 wire, the lower U terminal is internally jumped to the Rc terminal. In this application, hook up one wire from the vent damper to the U terminal and the other to the common side of the cooling system transformer.

Wiring

NOTES:

1 Available wiring configurations differ by product models/product numbers.
2 Use 18- to 22- gauge thermostat wire. Shielded cable is not required.
3 Set the R Slider Tab on the UWP to the up position (1 wire) for 1 transformer systems other down position (2 wires) for 2 transformer systems.
4 Set the U Slider Tab to the up position (1 wire) for non-powered ventilation or the down position (2 wires) for powered ventilation.

Conventional systems

1H/1C System (1 transformer)

R Power

Rc [R+Rc joined by Slider Tab]

Y Compressor contactor

C 24VAC common

W Heat relay

G Fan relay

1H/1C System (2 transformers)

R Power (heating transformer)

Rc Power (cooling transformer)

Y Compressor contactor

C 24 VAC common from cooling transformer

W Heat relay

G Fan relay

2H/2C System (1 transformer)

R Power

Rc [R +Rc joined by Slider Tab]

Y Compressor contactor (stage 1)

C 24VAC common

W Heat relay (stage 1)

G Fan relay

W2 Heat relay (stage 2)

Y2 Compressor contactor (stage 2)

Hot Water Relay Panel

R Power

Rc [R+Rc joined by Slider Tab]


W Heat Relay


C 24VAC common

NOTE: If the panel does not provide 24 volts AC at R and C ,set the slider to down position and wire a separate transformer to Rc and C.

Heat-only System with Fan

R Power

Rc [R +Rc joined by Slider Tab]

C 24VAC common

W Heat relay

G Fan relay

Cool-only System with Fan

R Power

Rc [R+Rc joined by Slider Tab]

Y Compressor contactor

C 24VAC common

G Fan relay

Heat pumps systems

1H/1C Heat Pump System

R Power
Rc [R+Rc joined by Slider Tab]
Y Compressor contactor
C 24VAC common
O/B Changeover valve
G Fan relay

2H/1C Heat Pump System

R Power
Rc [R+Rc joined by Slider Tab]
Y Compressor contactor
C 24VAC common
O/B Changeover valve
G Fan relay
Aux Auxiliary heat*
E Emergency heat relay*
L Heat pump fault input

NOTE: If dual fuel, TH6320WF2003 model needed.

2H/2C Heat Pump System

R Power
Rc [R+Rc joined by Slider Tab]
Y Compress or contactor(stage1)
C 24VAC common
O/B Changeover valve
G Fan relay
Y2 Compress or contactor(stage2)
L Heat pump fault input

3H/2C Heat Pump System

R Power
Rc [R+Rc joined by Slider Tab]
Y Compress or contactor(stage1)
C 24VAC common
O/B Changeover valve
G Fan relay
Aux Auxiliary heat*
E Emergency heat relay*
Y2 Compress or contactor(stage2)
L Heat pump fault input

NOTE: TH6320WF2003 only.

NOTE: Do NOT use W for heat pump applications. Auxiliary heat must wire to AUX or E.

If you do not have separate wires for the Aux and E terminals ,connect the wire to the Aux terminal.

Ventilation systems

NOTE: Ventilation is not available on all models.

Using U Slider Tab

Wired to ERV/HRV whole house ventilator with internal power supply.

Wired to fresh air damper powered by furnace transformer.

Mounting thermostat

1 Push excess wire back into the wall opening.
2 Close the UWP door. It should remain closed without bulging.
3 Align the UWP with the thermostat, and push gently until the thermostat snaps in place.
4 If needed, gently pull to remove the thermostat from the UWP

Installer setup – using the thermostat

Setup using the thermostat

• After the Lyric thermostat has powered up, touch START SETUP on the thermostat. You’ll be asked if you want to perform setup via Lyric app. Touch No.

• Touch or to toggle between Installer Set Up (ISU) options.

• Touch Edit or touch text area, and then touch or to edit default setup option.
• Touch Done or touch text area to confirm the setting or press Cancel.
• Touch or to continue to setup another ISU option.

Installer setup – using the Lyric app

Setup using the Lyric app

Download the Lyric app from App Store or Google Play to use a hidden PRO installation feature that will allow you to configure the thermostat and personally invite your customer to connect to the installed thermostat at the same time.

Enter Contractor Mode

To enter Contractor Mode, press and hold the Lyric logo for 5 seconds. Then tap Confirm to begin using Contractor Mode. Follow steps to personally invite your customer to connect their Lyric App.

Installer setup – advanced menu

To access the advanced menu, press and hold the Menu button for 5 seconds. Touch or to go through the options in the advanced menu.

Advanced menu options

Device Setup

This is used to access the device ISU setting.

Screen Lock

The thermostat touch screen can be set to lock fully or partially.

Rater View

A read only place to view all the ventilation settings.

System Test

Test the heating and cooling system.

Range Stop (Temperature)

Set the minimum, maximum, cool and heat temperature set points.

Reset

Access all reset options on the thermostat. This is the only place to access factory reset.

Key features

Note: Long press of Menu button for 5 seconds to access Advanced Menu options.

The screen will wake up by pressing the center area of the displayed temperature.
The screen will stay lit for 45 seconds. Brightness can be adjusted in the Menu.

#ISU ISU Name ISU Options (defaults in bold) Notes
120 Schedule Type No Schedule MO-SU = Every day the same  MO-FR, SA, SU = 5-1-1 schedule MO-FR, SA-SU = 5-2 schedule Each Day = Every day individualYoucanchange defaultMO-FR, SA-SUschedule here. Toeditperiods duringdays,temperature setpoints, orto  turn Schedule On/Off, from the home screen, go to MENU/SCHEDULE.
125 Temp Scale Fahrenheit, Celsius
130 Outdoor Temp No, Wired, Internet Select outdoortemperature data source. ThisISUautomatically defaultstoInternetwhenregisteredtoLyric  appandnowiredoutdoorsensorisselected.Werecommendusingawiredoutdoorsensor connectedtothe“S”  terminalsontheUWP.(See”Wiring”onpage5.) AnoutdoortemperatureisrequiredtosetthefollowingISUs:ISU355CompressorLockout,ISU356Aux  Heat Lockout, ISU 1013 Low Outdoor Temperature Ventilation Lockout, ISU 1014High Outdoor Temperature  Ventilation Lockout, and ISU 1015 High Outdoor Dew Point Ventilation Lockout.
200 System Type Conventional Forced Air Heat Pump  Boiler Cool OnlyBasic selection of system your thermostat will control.
205 Equipment Type Conventional Forced Air Heat: Standard Gas (STD GAS), High Efficiency Gas (EFF GAS),  Oil, Electric, Fan Coil* Heat Pump: Air To Air, Geothermal Boiler: Hot Water, SteamThis option selectsthe equipmenttype yourthermostat will control. Note: This option is NOT displayed if ISU  200issettoCoolOnly. * Fan coil setting is for a residential application with a hot water coil in an air-handler.
218 Reversing Valve 0/B on Cool, 0/B on Heat ThisISUisonlydisplayedifISU200issettoHeatPump. SelectwhetherreversingvalveO/Bshouldenergize  oncool oron heat
220 Cool Stages  (#200=Conv./  200=HP)0, 1, 2
221 Heat Stages/Aux/E  Stages (#200=Conv./  200=HP)Heat Stages: 0, 1, 2 AUX/E Stages: 0, 1Maximum of 2 Heat Stages for conventional systems. Maximum of 1 Aux/E stages for heat pump systems.
230 Fan Control Equipment, Thermostat This ISU is only displayed if ISU 205 is set to Electric Forced Air or Fan Coil.
253 Aux/E Control Both Aux/E, Either Aux/E Set “EITHER AUX/E” if you wantto setup and control Auxiliary and Emergency heating separately . ThisISUis  onlydisplayedifISU200issettoHeatPumpANDifISU221Aux/E stages=1.
255 Aux Heat Type Electric, Gas/Oil (or Fossil Forced Air) ThisISUis displayedonlyifISU200issettoheatpumpANDifISU221Aux/Eheatstages=1.  Note:OptionsofthisISUmayvarydependingonthemodel ofthe thermostat.
# ISU ISU Name ISU Options (defaults in bold) Notes
256 EM Heat Type Electric, Gas/Oil (or Fossil Forced Air) ThisISUis displayed only ifISU200 issettoHeatPump ANDifISU221Aux/E heatstages= 1 ANDifISU253  issettorunAUX/E heatseparately. Note: This ISU may not be available at all on some models.
260 Fossil Kit Control Thermostat, External(FossilFuelKitControlsBackup  Heat)ThisISUis displayedonly ifISU200issettoHeatPumpANDifISU221Aux/E heatstages= 1,ANDifISU256  issetto Gas/Oil. Note: This ISU may not be available at all on some models.
300 Auto Changeover On, Off OFF:Theusermustselectheatingorcoolingasneededtomaintainthedesired  indoor temperature. ON (Automatic):On(enabled) Allows usertoselectAutoChangeover as one ofthesystemmodesfrom  the home screen. In automode,the thermostat cancontrol either heating or cooling to maintain the desired  indoor temperature.
303 Auto Differential 0 °F to 5 °F or 0.0 °C to 2.5 °C Differential istheminimumnumber of degreesrise orfallrequired during off cycle toswitch fromthe last  activemode(heator cool)totheoppositemodewhenthe thermostatisinauto-changeover.Differential is  NOT deadband. The deadbandtemperature between whenheating (or cooling) cyclesonandcyclesoffto  maintain setpointis not adjustable.Honeywell uses an algorithmthatfixes deadbandat 0°F.
305 High Cool Stage  FinishYes, No ThisISUis only displayed when the thermostatissetto 2 coolstages. When setto YES, thisfeature keepsthe  higherstage ofthe coolingequipmentrunninguntilthe desiredsetpointisreached.
306 High Heat Stage  FinishYes, No ThisISUis only displayed when the thermostatissetto 2 ormore heatstages. When setto YES,thisfeature  keepsthe higherstage ofthe heatingequipmentrunninguntilthe desiredsetpointisreached.
340 Aux Heat Droop 0 = Comfort; 2 °F to 15 °F from setpoint (in 1 °F incre ments)or1.0°Cto7.5°Cfromsetpoint(in0.5°Cincrements)Auxheatdroopcanbesetonheatpumpsystemswithanauxiliaryheatstage.TheComfortsettingisNOT  availableforDualFuelsystems.Defaultsettingis0°F(Comfort)forElectricwhile2°FforGas/Oil.Theindoor  temperaturemustdroptotheselecteddroopsettingbeforethethermostatwillturnAuxHeaton.Forexample,  ifAuxHeatissetto2°F(1.0°C),theindoortemperaturemustbe2°F(1.0°C)awayfromthesetpointbefore  AuxHeatturnson.WhensettoComfort,the thermostat will useAuxHeat asneededtokeep the indoortem perature within 1 °F (0.5 ° C) degree of the setpoint.
350 Up Stage Timer Aux  HeatOff, 30, 45, 60, 75, 90 minutes 2, 3, 4, 5, 6, 8, 10, 12, 14, 16 hoursThe AuxiliaryHeat Upstage Timerstarts when the higheststage ofthe previous heating equipmenttype turns  on. Auxiliary heat will be used (if needed) when the timer expires. ThisISUis only displayed when ISU340 (AUX  HeatDroop)issetto2°Forhigher.
355 Balance Point  (Compressor Lockout)Off, 5°F to60°F (in5°F increments)or-15.0 °Cto15.5°C  (in2.5 °C or3.0 °C increments)Compressor Lockout requires an outdoor temperature. Set Compressor Lockout to the temperature below  whichitisinefficienttorunthe heatpump.When outside temperature isbelow thissetting,thermostatwill  lockoutheatpumpandrunAuxHeatonly.ThisISUisonlydisplayedifISU130=WiredorInternet,ISU200is  settoHeatPump,ISU221Aux/Estages=1,ANDISU260issettoThermostat.Werecommendusingawired  remote sensor as an outdoor temperature source. Defaultis40°FifISU205HeatingEquipmentisAirtoAirHeatPumpandISU255AuxHeatTypeisGas/Oil.  DefaultisOffifISU205HeatingEquipmentisAirtoAirHeatPumpandISU255AuxHeatTypeisElectric.  Default is Off if ISU 205 Heating Equipment is Geothermal. Compressor Lockout is optional for any type of heat pump (Air to Air Heat Pump, Geothermal Heat Pump).
# ISU ISU Name ISU Options (defaults in bold) Notes
356 AuxHeatLockOut  (AuxHeatOutdoor  Lockout)Off, 5 °F to 65 °F (in 5 °F increments) or -15.0 °C to 18.5 °C (in 2.5 °C or 3.0 °C increments)AuxHeat Lockoutrequires anoutdoortemperature. SetAuxHeat Lockouttooptimize energybills andtonot  allowittorunthemore expensiveAuxHeatsource above certainoutdoortemperature limit. ThisISUisonly  displayedifISU200issettoHeatPump,ANDISU260issettoThermostatcontrolANDifISU221Aux/E  stages=1.
365 Cool 1 CPH (Cooling  cycle rate stage 1)1 – 6 CPH (3 CPH) This ISU is only displayed when Cool/Compressor Stagesissetto1ormorestages.Cycleratelimitsthemaxi mum number of timesthe system can cycle in a 1 hour period measured at a 50% load. For example, when set  to3CPH,ata50%load,themostthesystemwillcycleis3timesperhour(10minuteson,10minutesoff).  The system cycles less often when load conditions are less than or greaterthan a 50% load.
366 Cool 2 CPH (Cooling  cycle rate stage 2)1 – 6 CPH (3 CPH) This ISU is only displayed when Cool /Compressor Stages is set to 2.
370 Heat 1 CPH (Heating  cycle rate stage 1)1 – 12 CPH ThisISUisonlydisplayedwhenHeatStagesissetto1stageormorestages.Cycleratelimitsthemaximum  numberoftimesthesystemcancycleina1hourperiodmeasuredata50%load.Forexample,whensetto3  CPH,ata50%load,themostthesystemwillcycleis3timesperhour(10minuteson,10minutesoff). The  systemcyclesless often when load conditions are lessthan or greaterthan a 50% load. The recommended  (default) cycleratesettingsarebelowforeachheatingequipmenttype: Standard Efficiency Gas Forced Air = 5 CPH; High Efficiency Gas Forced Air = 3  CPH; Oil Forced Air = 5 CPH; Electric Forced Air = 9 CPH; Fan Coil = 3 CPH; Hot  Water RadiantHeat = 3 CPH; Steam = 1 CPH.
371 Heat 2 CPH (Heating  cycle rate stage 2)1 – 12 CPH ThisISU is only displayed when Heat Stagesisset to 2 stages. The recommended (default) cycle rate settings  arebelowforeachheatingequipmenttype: Standard Efficiency Gas Forced Air = 5 CPH; High Efficiency Gas Forced Air = 3  CPH; Oil Forced Air = 5 CPH; Electric Forced Air = 9 CPH; Fan Coil = 3 CPH; Hot  Water RadiantHeat = 3 CPH; Steam = 1 CPH.
375 Aux Heat CPH  (Heating cycle rate  Auxiliary Heat)1 – 12 CPH ThisISUisonlydisplayedwhenISU200=HeatPumpandISU221=1.ItisonlydisplayedwhenAuxiliaryHeat  is configured.Therecommendedcycle ratesettingsarebelowforeachheatingequipmenttype: Standard Efficiency Gas Forced Air = 5 CPH; High Efficiency Gas Forced Air = 3  CPH; Oil Forced Air = 5 CPH; Electric Forced Air = 9 CPH.
378 EM Heat CPH  (Heating cycle rate  Emergency Heat)1 – 12 CPH ThisISUisonlydisplayedwhenEmergencyHeatisconfiguredandISU253:Aux/ETerminalControlissetto  controlAux andE heatIndependently. The recommendedcycle rate settings are belowfor eachheatingequip ment type: Standard Efficiency Gas Forced Air = 5 CPH; High Efficiency Gas Forced Air = 3  CPH; Oil Forced Air = 5 CPH; Electric Forced Air = 9 CPH.
387 Compressor  ProtectionOff, 1 – 5 minutes The thermostat has a builtincompressor protection(minimumofftimer)that preventsthe compressorfrom  restartingtooearlyafterashutdown.Theminimum-offtimerisactivatedafterthecompressorturnsoff.If  there is a call during theminimum-offtimer,the thermostatshows “Wait” inthe display. ThisISUis displayedif  ISU220issettoatleast 1stage.
390 Ext Fan Run Time  in CoolOff, 30, 60, 90 seconds 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15 minutesAfterthe callfor cooling ends,the thermostat keepsthe fan on forthe selectedamount oftime forincreased  efficiency.Thismayreintroducehumidityintothelivingspace.ThisISUis displayedifISU220issettoatleast  1stage.
# ISU ISU Name ISU Options (defaults in bold) Notes
391 Ext Fan Run Time  in HeatOff, 30, 60, 90 seconds 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15 minutesAfterthe callforheatingends,the thermostat keepsthe fan onforthe selectedamountoftime forincreased  efficiency.ThisISUisdisplayedifISU230issettoThermostatControlsFan.
425 Adaptive Recovery On, Off Adaptive IntelligentRecovery (AIR)is a comfortsetting.Heatingor coolingequipmentwillturnonearlier,  ensuringtheindoortemperaturewillmatchthesetpointatthescheduledtime.
429 Max Cool Temperature fromMin.CoolTemp.to99°Forto37.0°C(90°For32°C) The user cannot set the cooling temperature above this level.
430 Min Cool Temperature from50°For 10.0 °CtoMax.CoolTemp.(50 °F or 10 °C) The user cannot set the cooling temperature below this level.
431 Max Heat Temperature fromMin.HeatTemp.to90°Forto32.0°C(90°For32°C) The user cannot set the heating temperature above this level.
432 Min Heat Temperature from40°For4.4°CtoMax.HeatTemp.(50 °F or 10 °C) The user cannot set the heating temperature below this level.
500 Indoor Sensor Yes, No SetthisISUwhenyouwanttowirearemoteindoorsensortothe“S” terminalsontheUWP -see”Wiring”on  page5.ThisISUisonlydisplayedonlyifISU130issettoNOwiredoutdoorsensorconfigured
515 Sensor type 10k, 20k Choose resistance type of wired indoorsensor. ThisISUis only displayed when indoorsensoris configured ISU500.
520 Temperature Control Thermostat, Wired, Average ThisISUisonlydisplayedwhenindoorsensorisconfigured-ISU500.Youcanchoosewhattemperature  source tobe usedor youcanask thermostattouse both thermostat and remote sensorsfor higher accuracy of  measurement.
702 Air Filters 0 – 2 This ISU refers to the number of air filters in the system.
711 Air Filter 1 Reminder Off 10, 20, 30, 45, 60, 90, 120, 150 Run Time Days 30, 45, 60, 75 Days 3, 4, 5, 6, 9, 12, 15 MonthsChoose either calendar or equipment run time-based reminder.
712 Air Filter 2 Reminder Off 10, 20, 30, 45, 60, 90, 120, 150 Run Time Days 30, 45, 60, 75 Days 3, 4, 5, 6, 9, 12, 15 MonthsChoose either calendar or equipment run time-based reminder.
810 Hum Pad Reminder Off 6, 12 Calendar Months
921 Dehum Filter  ReminderOff 30, 60 Calendar Days 3 – 12 Calendar Months (in 1 month increments)
# ISU ISU Name ISU Options (defaults in bold) Notes
1000 Vent Type None, ERV/HRV, Passive, Fresh Air Damper None: The thermostat does not control ventilation. ERV/HRV:ThethermostatcontrolsanEnergyRecoveryVentilatororHeatRecoveryVentilatorforventila tion. Passive (FanOnly): Thethermostatturnsonthefanfor ventilation.Whensettopassivefan,thethermo stat does not control a damper or ventilator. The passive ventilation/passive fan setting only runsthe indoor  blowerfan. Thissetting doesnotopena damper orruna ventilator. Touse thissetting for ventilation,the home  wouldneedtobeset-upwitha pipefromoutdoorsintothereturnductthatiseitherpermanentlyopenorhasa  damperthatautomaticallyopenswhenevertheblowerfanison. Note: Some models only offer the passive fan setting.
1005 Vent Method ASHRAE 2010, ASHRAE 2013, Percent On Time Note: Options of this ISU may vary depending on the model of the thermostat.
1006 Vent Fan Control Thermostat, Equipment Thermostat: The thermostat turns on the ventilation and the fan when ventilation is needed. Equipment: Ventilation equipment controls the blower fan.
1007 Bedrooms 1 – 6 (2) This ISU is only displayed when ISU 1005 Ventilation Method is set to ASHRAE 2010 or 2013.
1008 Home Size 1000 – 5000 Sq. Ft. (1000 Sq. Ft.) This ISU is only displayed when ISU 1005 Ventilation Method is set to ASHRAE 2010 or 2013.
1009 Vent Rate 30 – 350CFM (in 5CFM increments) (150CFM) This ISU is only displayed when ISU 1005 Ventilation Method is set to ASHRAE 2010 or 2013.
1011 Vent Percent On Time 10% – 100% (30%) The thermostat operates ventilation equipment based on a percentage entered in the installer setup (ISU  1012). For example, if Percent on Time issetto 50%, the ventilation equipment willrun atrandomtimes dur inga1hourperioduntilitreachesa50%runtime(approximately30minutes).ThisISUisonlydisplayedif  ISU1005issettoPercentOnTime.
1012 Vent Priority Lockouts, ASHRAE Lockouts are Priority:ThethermostatplacesapriorityonlockoutsversustheASHRAEventilation  standard. The thermostatwill notrunventilationduring the following lockout conditions(if configured), unless  youmanuallycallforventilation: Lockout Ventilation during Outdoor Conditions (ISU 1013, 1014 and 1015). LockoutVentilationduring“Sleep” programperiods.Note:ThisoptionissetbytheuserontheVentilation  screenintheMenu. ASHRAE is Priority: ASHRAE requires additional ventilation following a long off cycle. The thermostat  meetsthe ASHRAE ventilationstandard by running additional ventilationwhen outdoor conditions are favor able.IfASHRAE cannotbemetwhenoutdoor conditionsarefavorable,thethermostatwilloverridetheoutdoor  lockoutsandrunventilation.Whenusingthisoption,itisrecommendedthatyouincreasetherate(CFM)of  the ventilationequipmenttomeettheASHRAE ventilationstandardina shorterruntime. The ability tolockout  ventilationduring the“Sleep” isnotanoptionwhenyouselectASHRAE isPriority.
1013 Low Outdoor Temp  Vent LockoutOff, -20 °F to -40 °F (in 5 °F increments) or -28.0 °C to -4.0 °C (in 2.0 °C increments)ISU130mustbesettoWiredorInternet.ThisISUisonlydisplayedwhenISU1000VentilationTypeissetto  ERV/HRVor FreshAirDamper.
1014 High Outdoor Temp  Vent LockoutOff, 80°F to110°F (in5°F increments)or  26°Cto44°C(in2°Cincrements)ISU130mustbesettoWiredorInternet.ThisISUisonlydisplayedwhenISU1000VentilationTypeissetto  ERV/HRV or Fresh AirDamper.
1015 High Outdoor  Dewpoint Vent  LockoutOff, 65°Fto85°F(in5°Fincrements)or  18°Cto30°C(in2°Cincrements)ISU130mustbesettoInternet.ThisISUisonlydisplayedifISU1000VentilationTypeissettoERV/HRVor  Fresh Air Damper.
#ISU ISU Name ISU Options (defaults in bold) Notes
1017 Vent Core Reminder Off, 3, 6, 9, 12 months This ISU is displayed only if ISU 1000 is set to ERV/HRV.
1018 Vent Filter Reminder Off, 3, 6, 9, 12 months
1100 UV Devices 0 – 2 SomesystemsmayhavetwoUVdevices,onefortheA-CoilandanotherforAirTreatment.Areplacement  remindercanbesetupforeachoneseparately.
1105 UV Bulb 1 Reminder Off, 6, 12, 24 months
1106 UV Bulb 2 Reminder Off, 6, 12, 24 months
1401 Idle Brightness 0= Off, 0 – 5 Adjust brightness of an inactive backlight(idle screen) fromdefault 0 (backlight off) to 5 (maximum  brightness).
1410 Clock Format 12 hour, 24 hour
1415 Daylight Saving On, Off Set to Off in areas that do not follow Daylight Saving Time.
1420 Temp Offset Off, -3 °F to 3 °F (in 1 °F increments) or -1.5 °C to 1.5 °C (in 0.5 °C increments)0°F -No difference in displayed temperature and the actualroomtemperature. The thermostat candisplayup  to 3 °F (1.5 C) lower or higherthan the actualmeasured temperature.

Performing a system test

You can test the system setup in ADVANCED MENU under SYSTEM TEST option.

1 Press and hold Menu on the Lyric thermostat for 5 seconds to access ADVANCED MENU options.
2 Touch or to go to SYSTEM TEST.
3 Touch Select or touch text area.
4 Touch or to select system test type. Touch Select or touch text area.
5 For the heat test and cool test, use or to activate each stage of the equipment. For the fan test, use or to turn the fan on and off.

NOTE: The clock is used as a timer while the stages are running. The Heat On and Cool On indicators are displayed when the system test
is running.

Viewing equipment status

You can see the status of thermostat controlled equipment in the Menu under the EQMT STATUS option.

1 Touch Menu on your thermostat.
2 Touch or to go to EQMT STATUS. Touch Select or touch text area.
3 Touch or to view statuses of all the equipment the thermostat is controlling. Depending on what feature the thermostat supports or how it was installed, the Equipment Status screen reports data for the following systems:

• Heating and cooling
• Fan
• Ventilation (available on certain models only)

Troubleshooting

Screen is blank

• Check circuit breaker and reset if necessary.

• Make sure power switch at heating and cooling system is on.
• Make sure furnace door is closed securely.

Screen is difficult to read

• Change screen brightness in thermostat Menu. Increase brightness intensity for inactive back light of the thermostat screen(max.islevel5).

Heating or cooling system does not respond

• Touch Mode to set system to Heat. Make sure the temperature is set higher than the Inside temperature.

• Touch Mode to set system to Cool. Make sure the temperature is set lower than the Inside temperature.
• Check circuit breaker and reset if necessary.
• Make sure power switch at heating &cooling system is on.
• Make sure furnace door is closed securely.

Heat runs with cooling

• Verify there is not a wire attached to W for heat pump systems.

Alerts and reminders

Alerts and reminders are displayed via the alert symbol and alert number in the clock area on the home screen. You can read more information about active alerts, snooze or dismiss non-critical alerts in Menu/Alerts.

Number Alert/Reminder Definition
164 Heat Pump Needs  ServiceHeat pump needs service. Contact dealer to diagnose  and service heat pump.
168 Wi-Fi Radio Error Wireless module is not operating. Wireless features  are not available. Please contact dealer to replace the thermostat.
170 Internal Memory Error The memory of the thermostat has encountered an  error. Please contact dealer for assistance.
171 Set the Date and Time Set the date and time on your thermostat. The date and  time are required for certain features to operate, like the  program schedule.
173 Thermostat  Temperature Sensor  ErrorThe sensor of the thermostat has encountered an error.  Please contact dealer to replace the Thermostat.
175 AC Power Resumed AC power resumed to thermostat after power loss.
177 Indoor Temperature  Sensor ErrorWired indoor temperature sensor is not connected  or there is a wiring short. Please contact dealer for  assistance.
178 Outdoor Temperature  Sensor ErrorWired outdoor temperature sensor is not connected  or there is a wiring short. Please contact dealer for  assistance.
181 Replace Air Filter (1) Replace air filter (1). Reset the timer by touching  the “dismiss” button on thermostat screen after it is  replaced

Alerts and remnders 

Number Alert/Reminder Definition
182 Replace Air Filter (2) Replace air filter (2). Reset the timer by touching  the “dismiss” button on thermostat screen after it is  replaced.
183 Clean Humidifier Tank  and Replace Water  FilterClean humidifier tank and replace the water filter, or  contact dealer to do this for you. Reset the timer by  touching the “dismiss” button on the thermostat screen  after it is replaced.
184 Replace Humidifier  PadReplace humidifier pad. Reset the timer by touching  the “dismiss” button on the thermostat screen after it is  replaced.
185 Replace Dehumidifier  FilterReplace the dehumidifier filter. Reset the timer by  touching “dismiss” button on thermostat screen after it is replaced.
186 Clean Ventilator Core Clean ventilator core. Reset the timer by touching  the “dismiss” button on thermostat screen after it is replaced.
187 Clean or Replace  Ventilator FilterClean or replace ventilator filter. Reset the timer by  touching the “dismiss” button on thermostat screen  after it is replaced.
188 Replace UV Bulb (1) Replace UV Bulb (1). Reset the timer by touching  the “dismiss” button on thermostat screen after it is  replaced.
189 Replace UV Bulb (2) Replace UV Bulb (2). Reset the timer by touching  the “dismiss” button on thermostat screen after it is  replaced.
210 Register Online For  Outdoor TemperatureOnline registration is required to receive outdoor  temperature from the Internet. Outdoor temperature  is needed for your current system setup. Download the Lyric app to register your thermostat.
388 Register Online for  Remote Access and  Outdoor TemperatureOnline registration is required for remote access  and out door temperature .Download the Lyric app to  registery our thermostat.
399 No Internet The connection to the Internet has been lost. Please  check your network settings.
400 No Wi-Fi Signal The Wi-Fi signal has been lost. Please wait for the  thermostat to reconnect or select a new Wi-Fi network.  Follow steps in the Lyric app
508 Wi-Fi Not Configured Please download the Lyric app and follow the steps to  connect thermostat to your Wi-Fi network.

CAUTION: ELECTRICAL HAZARD
Can cause electrical shock or equipment damage. Disconnect power before beginning installation.
CAUTION: EQUIPMENT DAMAGE HAZARD
Compressor protection is bypassed during testing. To prevent equipment damage, avoid cycling the compressor quickly.
CAUTION: MERCURY NOTICE
If this product is replacing a control that contains mercury in a sealed tube, do not place the old control in the trash. Contact your local waste management authority for instructions regarding recycling and proper disposal.

Specifications

Temperature Ranges

Heat: 40 °F to 90 °F (4.5 °C to 32.0 °C)
Cool: 50 °F to 99 °F (10.0 °C to 37.0°C)

Operating Ambient Temperature

37 °F to 102 °F (2.8 °C to 38.9 °C)

Shipping Temperature

-20 °F to 120 °F (-28.9 °C to 48.9 °C)

Operating Relative Humidity

5% to 90% (non-condensing)

Physical Dimensions in inches (mm) (H x W x D)

Lyric T6 PROWi-Fi Thermostat(TH6320WF2003):
4-5/64 x 4-5/64 x 1-1/16 (104 x 104 x 27)
Lyric T6 PRO Wi-Fi Thermostat (TH6220WF2006):
4-5/64 x 4-5/64 x 1-1/16 (104 x 104 x 27)
UWP Mounting System (included):
2-9/32 x 2-13/64 x 2-43/64 (58 x 56 x 10)
Standard Installation Adapter (THP2400A1076):
3-29/32 x 3-57/64 x 21/32 (99 x 99 x 17)
Decorative Cover Plate – Small (included):
4-49/64 x 4-49/64 x 11/32 (121 x 121 x 9)
Decorative Cover Plate – Large (THP2400A1068):
6-7/64 x 6-7/64 x 9/32 (155 x 155 x 7)

Electrical Ratings 

Terminal Voltage  (50/60Hz)Running  Current
W Heating 20-30 Vac 0.02-1.0 A
(Powerpile) 750 mV DC 100 mA DC
W2 (Aux) Heating 20-30 Vac 0.02-1.0 A
E Emergency Heat 20-30 Vac 0.02-0.5 A
Y Compressor Stage 1 20-30 Vac 0.02-1.0 A
Y2 Compressor Stage 2 20-30 Vac 0.02-1.0 A
G Fan 20-30 Vac 0.02-0.5 A
O/B Changeover 20-30 Vac 0.02-0.5 A
L/A Input 20-30 Vac 0.02-0.5 A
20-30 Vac 0.02-0.5 A

5-year limited warranty

For Warranty information go to http://customer.honeywell.com

Power Consumption
Backlight On: 1.48VA
Backlight Off: 0.88VA

Regulatory information

FCC REGULATIONS § 15.19 (a)(3)

This device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions:
1 This device may not cause harmful interference, and
2 This device must accept any interference received, including interference that may cause undesired operation.

IC REGULATIONS RSS-GEN

This device complies with Industry Canada’s license-exempt RSSs.

Operation is subject to the following two conditions:
1 This device may not cause interference; and
2 This device must accept any interference, including interference that may cause undesired operation of the device.

FCC Warning (Part 15.21) (USA only)

Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.

You can download the PDF version of the Honeywell LyricTM T6ProWi-fi programmable Thermostat user manual here.